PGF3 Manuals


Installation Instructions For Natural Gas Conversion
(Kit Part No. 1173865)
This kit is designed for conversion to Natural Gas.
Natural Gas Orifice Kits and Sizes
Table 1
Elevation Above Sea Level
0 to 2000 ft
2001 to 4000 ft 4001 to 5000 ft
5001 to 6000 ft
6001 to 7000 ft
7001 to 8000 ft
8001 to 9000 ft 9001 to 10000 ft
Orifice Drill # 
Orifice Drill # 
Orifice Drill # 
Orifice Drill # 
Orifice Drill # 
Orifice Drill # 
Orifice Drill # 
Model Number
Orifice Drill #
Kit Number
(Field-Supplied) (Field-Supplied) (Field-Supplied) (Field-Supplied) (Field-Supplied) (Field-Supplied) (Field-Supplied)
PGAA, PGMD (All Sizes)
44
1173863
45
46
47
47
48
48
49
PGAD, PGME (All Sizes)
44
1173863
45
46
47
47
48
48
49
PGX3, PDX3 (All Sizes)
44
1173863
45
46
47
47
48
48
49
PGC***K040F, GPCM**K040
44
1173863
45
46
47
47
48
48
49
PGC***K060F, GPCM**K060
44
1173863
45
46
47
47
48
48
49
PGC***K080F, GPCM**K080
44
1173863
45
46
47
47
48
48
49
PGC***K100F, GPCM**K100
41
1173865
43
43
43
44
44
45
46
PGC***K120F, GPCM**K120
42
1173865
43
43
44
44
45
46
47
PGC***K140F, GPCM**K140
42
1173865
43
43
44
44
45
46
47
PGF***K040F, GPFM**K040
44
1173863
45
46
47
47
48
48
49
PGF***K060F, GPFM**K060
44
1173863
45
46
47
47
48
48
49
PGF***K080F, GPFM**K080
44
1173863
45
46
47
47
48
48
49
PGF***K100F, GPFM**K100
41
1173865
43
43
43
44
44
45
46
PGF***K120F, GPFM**K120
42
1173865
43
43
44
44
45
46
47
PGF***K140F, GPFM**K140
42
1173865
43
43
44
44
45
46
47
PGS***K040F, GPSM**K040
44
1173863
45
46
47
47
48
48
49
PGS***K060F, GPSM**K060
44
1173863
45
46
47
47
48
48
49
PGS***K080F, GPSM**K080
44
1173863
45
46
47
47
48
48
49
PGS***K100F, GPSM**K100
41
1173865
43
43
43
44
44
45
46
PGS***K120F, GPSM**K120
42
1173865
43
43
44
44
45
46
47
PGS***K140F, GPSM**K140
42
1173865
43
43
44
44
45
46
47
PGF3**040
44
1173863
45
46
47
47
48
48
49
PGF3**060
44
1173863
45
46
47
47
48
48
49
PGF3**080
44
1173863
45
46
47
47
48
48
49
PGF3**100
41
1173865
43
43
43
44
44
45
46
PGF3**120
42
1173865
43
43
44
44
45
46
47
PGF3**140
42
1173865
43
43
44
44
45
46
47
Note: "**" or "***" may be any combination of numbers and/or letters in the model number.
Note: The orifice sizes in the chart above derate the input rate at 4% per 1000 feet above sea level for altitudes exceeding 2000 feet above sea level.
Natural gas data is based on .60 specific gravity, a heating value of 1030 Btu/cubic foot, and 3.5 "W.C. manifold pressure.
For fuels with different specific gravity and/or different heating values, consult the National Fuel Gas Code ANSI Z223.1 - 2002/NFPA 54-2002 or
National Standard of Canada, Natural Gas and Propane Instal ation Code CSA B149.1-00.
Note:  If converting from LP gas to Natural gas at altitudes exceeding 2000 feet above sea level,  conversion kit (Part #330732-401) is required for proper conversion.  For all models, except PGX3, PDX3, and PGF3, a .018 pilot 
orifice (Part # 5032110) is also required.
Parts ListKit # 1173865
Installing and servicing heating equipment can be hazardous due
Description
Part #
Qty
to gas and electrical components. Only trained and qualified
Burner Orifice #41
1096942
7
personnel should install, repair, or service heating equipment.
Burner Orifice #42
1011351
7
Untrained service personnel can perform basic maintenance
Pilot Orifice (0.018)
503211
1
functions such as cleaning and replacing air filters. All other
Honeywell Conv. Kit #396222
1172952
1
operations must be performed by trained service personnel. When
Label, Natural Gas Conversion
1173866
1
working on heating equipment, observe precautions in the
Label, Field Conversion
1009678
1
Instructions
462 06 1211 00
1
literature, on tags, and on labels attached to or shipped with the
appliance and other safety precautions that may apply.
SAFETY REQUIREMENTS
Follow all safety codes. In the United States, follow all safety codes
including the National Fuel Gas Code (NFGC) ANSI
Recognize safety information. This is the safety- alert symbol .
Z223.1- 2006/NFPA 54- 2006. In Canada, refer to the of the
When you see this symbol in instruction manuals be alert to the
National Standard of Canada Natural Gas and Propane
potential for personal injury.
Installation Code (NSCNGPIC) CSA B149.1- 05. Wear safety
glasses and work gloves. Have fire extinguisher available during
Understand the signal words DANGER,WARNING, or CAUTION.
start- up and adjustment procedures and service calls.
These words are used with the safety- alert symbol. DANGER
identifies the most serious hazards, those that will result in severe
These instructions cover minimum requirements and conform to
personal injury or death. WARNING signifies a hazard that could
existing national standards and safety codes. In some instances,
result in personal injury or death. CAUTION is used to identify
these instructions exceed certain local codes and ordinances,
unsafe practices that may result in minor personal injury or product
especially those that may not have kept up with changing
and property damage. NOTE is used to highlight suggestions that
residential construction practices. We require these instructions
will result in enhanced installation, reliability, or operation.
as a minimum for a safe installation.
462 06 1211 00
- 1 -
3/17/06


Big size of image:

Please install Flash player from http://get.adobe.com/flashplayer/!

39 39 45 45

Designated trademarks and brands are the property of their respective owners | Disclaimer