Incandescent Dimmer Module RDM-INC Manuals




Installation Sheet
RDM-INC Incandescent Dimmer Module
2400 W
The RDM-INC Incandescent Dimming Module is designed for use with the 

Test loads for shorts before connecting.
RDA series of enclosures, in a AMX Lighting™ modular digital dimming 

Use low voltage wires with a 300 volt rating or greater.
system. It is a standard 2400 W incandescent dimmer. It can dim incandes-

Use field installed copper conductors.
cent lights, cold-cathode, neon and two-wire dimmable ballasts. The RDM-

Run all low-voltage and control wires away from heat producing parts 
INC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL 
of the dimmer.
approved.

Each dimming circuit must have a separate neutral connection.
Mounting

All electrical ratings are for continuous duty.
points

AC lighting loads only.

For indoor use only.
Line In
High-voltage

This module may require extra power from the AXlink connection or an 
connections
Line Out
external power supply connected to the control card.
Connecting the RDM-INC to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-INC four-pin module connector
350µS
2 (-)
Choke
1 (+)
4-pin plug from a RDM series module
Note: The 4-pin plugs from the module
connector to the 4-pin connector on the
master (black plug cover facing up).

FIG. 2  Connecting the RDM-INC to the AMX Lighting Master
Lighting Application Drawing
20 A power device
All neutrals are common
to the Neutral block in the
enclosure. Provide a 
separate neutral for each
load.
Line in
Low-voltage control
(HOT)
Load
wiring: 4-pin
connector to AMX 
 
Lighting master
controller
FIG. 1  RDM-INC
 
Neutral
RDM-INC UL and C-UL Ratings:
Load

120 VAC, 50/60 Hz, 2400 W
Neon lights

240/277 VAC, 50/60 Hz, 2400 W
Circuit breaker
(cold-cathode, on/off)
panel
Suggested Dimmed Loads:

Incandescent
Neutral

Low-voltage

Neon, cold-cathode
Load

Two-wire, phase-controlled ballast
Two-wire dimmable ballast
Specifications:
FIG. 3  Sample wiring diagram

Dimensions (HW): 10.0" x 2.75" (25.4 cm x 6.985 cm)

Phase dependant

Use wires rated at 75°C (167°F)

Torque terminals to 7 in-lbs. (0.8 N/M)

Max. wire size: 10 AWG (4 mm²)

Wire stripping length: 0.28" (7 mm)

Weight: 3.7 lbs. (1.67 kg)

BTU/hr: 300

Control current: 45 mA @ 12 VDC

Choke: 350 µS Rise time @ 120 VAC
            175 µS Rise time @ 240 VAC
Caution: Pre-Installation Notes:

All Class 1 wiring must be connected to proper terminals.

All control wiring must be connected to proper terminals.

Disconnect power while installing or connecting unit.