2WT-B Manuals


1. Remove the detector cover by turning counterclockwise. (See
Figure 6: Removing/Replacing Screen/Sensing Chamber
Figure 6.)
2. Vacuum the cover or use canned air to remove any dust or
REMOVABLE
DETECTOR
debris.
COVER
3. Remove the top half of the screen/sensing chamber by lifting
straight up (Figure 6).
4. Vacuum or use canned air to remove any dust or particles that
SCREEN/SENSING
CHAMBER
are present on both chamber halves.
(TOP HALF)
5. Replace the top half of the screen/sensing chamber by align-
ing the arrow on the screen/sensing chamber with the arrow
on the housing. Press down firmly until the screen/sensing
chamber is fully seated.
6. Replace the detector cover by placing it over the screen/sensing
DETECTOR
chamber and turning it clockwise until it snaps into place.
HOUSING
S0136-00
7. Reinstall the detector and test. (See the Testing section.)
8. Notify the proper authorities when the system is back in service.
Electrical Specifications 2-wire 4-wire
Physical Specifications
System Voltage – Nominal:  12/24  12/24 Volts Non-polarized
Heat Sensor
Min.: 8.5 
8.5 
Volts
   (Model 2WT-B and 4WT-B):  135°F (57.2°C)
Max.: 35 
35 
Volts
Freeze Trouble
Max. Ripple Voltage: 30  
30 
% peak to peak
   (Model 2WT-B and 4WT-B):  41°F (5°C)
  
of applied voltage
Operating Temperature Range:
Max. Standby Current: 50 
50 
µA average
   2W-B and 4W-B: 
32 to 120°F (0 to 49°C)
Peak Standby Current: 100 
— 
µA
   2WT-B and 4WT-B: 
32 to 100°F (0 to 37.8°C)
Max. Alarm Current: 130 
20 
mA 12 Volt Systems
Operating Humidity Range: 0 to 95% RH non-condensing
(For 2W-B and 2WT-B,
Storage Temperature Range: –4 to 158°F (–20 to 70°C)
   panel must limit current)  130 
23  mA 24 Volt Systems
Diameter (including base): 5.3 inches
Alarm Contact Ratings: — 
0.5 
Amp @ 30 V AC/DC
Height (including base): 2.0 inches
Alarm Reset Time: 0.3 
0.3 
sec
Weight:  
6.3 oz.
Max. Start-up Capacitance: 0.1 
— µF
Latching Alarm:          Reset by momentary power interruption
Maximum Initial
   Start-up Time:   
45 
15  sec
Alarm Verification*
   Start-up Time:   
15 
15  sec
*Assumes the panel’s alarm verification reset time is 10 seconds or less. Should the alarm verification reset exceed 10 seconds, use the maximum initial start-up time.
Please refer to insert for the Limitations of Fire Alarm Systems
Three-Year Limited Warranty
System Sensor warrants its enclosed smoke detector to be free from defects in
Repair Department, RA #__________, 3825 Ohio Avenue, St. Charles, IL 60174.
materials and workmanship under normal use and service for a period of three
Please include a note describing the malfunction and suspected cause of failure.
years from date of manufacture. System Sensor makes no other express war-
The Company shall not be obligated to repair or replace units which are found to
ranty for this smoke detector. No agent, representative, dealer, or employee of
be defective because of damage, unreasonable use, modifications, or alterations
the Company has the authority to increase or alter the obligations or limitations
occurring after the date of manufacture. In no case shall the Company be liable for
of this Warranty. The Company’s obligation of this Warranty shall be limited to
any consequential or incidental damages for breach of this or any other Warranty,
the repair or replacement of any part of the smoke detector which is found to
expressed or implied whatsoever, even if the loss or damage is caused by the
be defective in materials or workmanship under normal use and service during
Company’s negligence or fault. Some states do not allow the exclusion or limita-
the three year period commencing with the date of manufacture. After phon-
tion of incidental or consequential damages, so the above limitation or exclusion
ing System Sensor’s toll free number 800-SENSOR2 (736-7672) for a Return
may not apply to you. This Warranty gives you specific legal rights, and you may
Authorization number, send defective units postage prepaid to: System Sensor,
also have other rights which vary from state to state.
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable  protection against harmful interference in a residential installation. This equipment generates,  uses and can radiate radio frequency energy and, if
not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference
will not occur in a particular installation.  If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
  
– Reorient or relocate the receiving antenna.
  
– Increase the separation between the equipment and receiver.
  
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  
– Consult the dealer or an experienced radio/TV technician for help.
D100-96-00 4
I56-1800-08R
©2005 System Sensor