Figure 1: Mounting of Detector
Wiring Installation Guidelines
All wiring must be installed in compliance with the National
Electrical Code, applicable state and local codes, and any special
requirements of the local Authority Having Jurisdiction.
Proper wire gauges should be used. The conductors used to con-
nect smoke detectors to the alarm control panel and accessory
devices should be color-coded to reduce the likelihood of wiring
errors. Improper connections can prevent a system from respond-
S0121-00
ing properly in the event of a fire.
The i3 Series heads and bases are keyed so that a 2-wire head will
The screw terminals in the mounting base will accept 14–22
only mount to a 2-wire base, and a 4-wire head will only mount
gauge wire. For best system performance, all wiring should be
to a 4-wire base. The heads and bases are clearly identified as
installed in separate grounded conduit; do not mix fire alarm
either 2-wire or 4-wire. When mounting the i3 Series, ensure that
system wiring in the same conduit as any other electrical wiring.
the head is mounted to the correct base.
Twisted pair may be used to provide additional protection against
Tamper-Resistant Feature
extraneous electrical interference.
The i3 Series detectors include a tamper-resistant feature that
Wire connections are made by stripping approximately 1⁄4-inch
prevents removal from the mounting base without the use of a
of insulation from the end of the feed wire, inserting it into the
tool. To engage the tamper-resistant feature, cut the small plastic
proper base terminal, and tightening the screw to secure the wire
tab located on the mounting base (Figure 2), and then install the
in place.
detector. To remove the detector from the base once it has been
made tamper resistant, use a small screwdriver to depress the
Two-Wire Compatibility
square tamper release tab, located on the skirt of the mounting
System Sensor two-wire smoke detectors are marked with a
base, and turn the detector counterclockwise.
compatibility identifier located on the label on the back of the
product. For two-wire models 2W-B and 2WT-B, connect detectors
Figure 2: Tamper-Resistant Feature
only to compatible alarm control panels as identified by System
DIRECT MOUNT
Sensor’s compatibility chart. This chart contains the current list of
HOLES
detectors and UL Listed compatible control units. A copy of this
list is available from System Sensor upon request.
Wiring Diagrams
Figure 3a: Wiring Diagram, 2W-B and 2WT-B
2-WIRE +
EOL
SNAP OFF TAB
ZONE

RESISTOR
FOR TAMPER LOCK
RA400Z
RA400Z
TAMPER
RELEASE TAB
S0226-00
(
(
(
(
(
1
2
3
4
5
(
(
(
(
(
1
2
3
4
5
)
)
)
)
)
)
)
)
)
)
Do NOT Install Detectors in the Following Areas:
2-WIRE
 + IN
 + OUT
 – IN/OUT
 RA
 RA
 + IN
 + OUT
 – IN/OUT
 RA
 RA
CONTROL
+

+

• In or near areas where particles of combustion are normally
PANEL
present such as kitchens; in garages (vehicle exhaust); near
2W-B or
2W-B or
furnaces, hot water heaters, or gas space heaters.
2WT-B
2WT-B
S0133-00
• In very cold or very hot areas.
• In wet or excessively humid areas, or next to bathrooms with
Figure 3b: Wiring Diagram, 4W-B and 4WT-B
showers.
• In dusty, dirty, or insect-infested areas.
AUX OR +
EOL
SMOKE
RELAY
• Near fresh air inlets or returns or excessively drafty areas. Air
POWER –
(A77-716B)
conditioners, heaters, fans, and fresh air intakes and returns

IDC
+
can drive smoke away from the detector.
EOL
RESISTOR
Consult NFPA 72, the local Authority Having Jurisdiction (AHJ),
(
(
(
(
(
1
2
3
4
5
(
(
(
(
(
1
2
3
4
5
)
)
)
)
)
 + IN
 + OUT
 – IN/OUT
 NO
 COM
)
)
)
)
)
 + IN
 + OUT
 – IN/OUT
 NO
 COM
and/or applicable codes for specific information regarding the
4-WIRE
CONTROL
spacing and placement of smoke detectors.
PANEL
4W-B or
4W-B or
CAUTION
4WT-B
4WT-B
S0134-00
Smoke detectors are not to be used with detector guards unless
the combination has been evaluated and found suitable for that
purpose.
D100-96-00 2