2WT-B Manuals


INSTALLATION AND MAINTENANCE INSTRUCTIONS
Series
3825 Ohio Avenue, St. Charles, Illinois 60174
Photoelectric Smoke Detector
1-800-SENSOR2, FAX: 630-377-6495
Models:
2W-B, 2WT-B
www.systemsensor.com
4W-B, 4WT-B
Before Installing
Please read thoroughly System Sensor manual A05-1003,
Two LEDs on the detector provide a local visual indication of the
Applications Guide for System Smoke Detectors, which provides
detector’s status:
detailed information on detector spacing, placement, zoning, wir-
Table 1: Detector LED Modes
ing, and special applications. Copies of this manual are available
Green LED
Red LED
from System Sensor at no charge.
Power-up
Blink 10 sec
Blink 10 sec
NOTICE: This manual shall be left with the owner/user of this
Normal (standby)
Blink 5 sec

equipment.
Out of sensitivity

Blink 5 sec
IMPORTANT: This detector must be tested and maintained regu-
Freeze Trouble

Blink 10 sec
larly following NFPA 72 requirements. At a minimum, cleaning
Alarm

Solid
should be performed annually.
After an initial power-up delay, the red and green LEDs will blink
General Description
synchronously once every ten seconds. It will take approximately 80
Models 2W-B and 2WT-B are 2-wire photoelectric smoke detec-
seconds for the detector to finish the power-up cycle (see Table 2).
tors; models 4W-B and 4WT-B are 4-wire photoelectric smoke
Table 2: Power-up Sequence for LED Status Indication*
detectors. All models incorporate a state-of-the-art optical sensing
Condition
Duration
chamber and an advanced microprocessor. The microprocessor
Initial LED Status Indication
80 seconds
allows the detector to automatically adjust its sensitivity back
Initial LED Status Indication
4 minutes
to the factory setting when it becomes more sensitive due to
(if excessive electrical noise is present)
contaminants settling in its chamber. In order for this feature
*Refer to Electrical Specifications for start-up time in conjunction with panel alarm
to work properly, the chamber must never be opened while
verification.
power is applied to the smoke detector. This includes cleaning,
NOTE: If, during power-up, the detector determines there is
maintenance or screen replacement. Should it become necessary,
excessive electrical noise in the system such as those caused by
the screen/sensing chamber is field replaceable. Models 2WT-B
improper grounding of the system or the conduit, both LEDs will
and 4WT-B also feature a restorable, built-in, fixed temperature
blink for up to 4 minutes before displaying detector status (see
(135°F) thermal detector and are also capable of sensing a freeze
Table 2).
condition if the temperature is below 41°F.
After power-up has completed and the detector is functioning
All i3 Series detectors are designed to provide open area protec-
normally within its listed sensitivity range, the green LED blinks
tion. Two-wire models must be used with compatible UL Listed
once every five seconds. If the detector is in need of maintenance
panels only.
because its sensitivity has shifted outside the listed limits, the red
When used with an i3 Series compatible control panel or the i3
LED blinks once every five seconds. When the detector is in the
Series 2W-MOD module (refer to installation manual D500-46-00),
alarm mode, the red LED latches on. The LED indication must not
the 2W-B and 2WT-B are capable of generating a “maintenance
be used in lieu of the tests specified under Testing. In a freeze
needed” signal. The 2W-MOD can indicate a need for cleaning,
trouble condition, the red LED will blink once every 10 seconds
replacement, or a freeze condition (2WT-B only) at the control
(refer to Table 1).
panel or module.
To measure the detector’s sensitivity, the i3 Series Model SENS-
Installation of the 2W-B, 2WT-B, 4W-B, and 4WT-B detectors is
RDR Infrared Sensitivity Reader tool (see Figure 4) should be
simplified by the use of a mounting base that may be pre-wired
used.
to the system, allowing the detector to be easily installed or
Models 2W-B and 2WT-B also include an output that allows an
removed. The mounting base installation is further simplified by
optional Model RA400Z Remote Annunciator to be connected.
the incorporation of features compatible with drywall fasteners.
Mounting
Each i3 Series detector is supplied with a mounting base that can
be mounted:
1. To a single gang box, or
2. To a 31⁄2-inch or 4-inch octagonal box, or
3. To a 4-inch square box with a plaster ring, or
4. Direct mount or to ceiling using drywall fasteners (Figure 2).
D100-96-00 1